AN021 - Connector wiring

1. Types of connectors

FamilyWire section
without caps
Wire section
with caps
Contact
features
BLZF 3.500,3÷1,50 mm20,3÷1 mm2
Self-locking spring contact
B2L 3.500,3÷1,00 mm20,3÷0,5 mm2
B2CF 3.500,14÷1,50 mm20,14÷1,50 mm2
BLZF 5.080,3÷2,50 mm20,3÷2,00 mm2
BLF 5.000,2÷2,50 mm20,3÷2,00 mm2
BLZ 5.000,2÷2,50 mm20,1÷1 mm2
Screw contact

MSTB 2.5
MSTBT 2.5
0,2-2,5mm2 0,25-2,5mm2

1.1 BLZF 3.50

1.1.1 Further notes

1.2 B2L 3.50

1.2.1 Further notes

1.3 B2CF 3.50

1.3.1 Further notes

1.4 BLF 5.00

1.4.1 Further notes

Terminal 10 mm, stripping length 12 mm

1.5 MSTB 2.5

Connectable conductors

:info:For most safer wiring, we recommend the use of Caps

2. Tools

2.1 Caps

Wire sectionPlunger sectionBrandModel
0,1÷0,3 mm20,95 mm2CembrePKE 308
0,3÷0,5 mm21,32 mm2CembrePKE 508
BMBM00601
1 mm22,5mm2BM00603PK 108
BMBM00603

2.2 Caps crimping Pliers

Model: “Cembre ND#4 cod. 2590086”

2.3 Screwdriver

2.3.1 Screwdriver for self-locking spring terminals:

Flat blade Screwdriver according to DIN 5264-A.

A = 0,6mm
B = 2,5mm max
C = 7 mm min

2.3.2 Screwdriver for screw terminals

Flat blade Screwdriver According to DIN 5264. Tightening torque: 0,4 ÷ 0,5 Nm.

A = 0,6mm
B = 3,5mm

3. Procedures

3.1 BLZF, B2L, BLZF e BLF

Discover the copper wire for 10mm
Insert the plunger and tighten it with the appropriate clamp
a) Insert the screwdriver without rotate it
b) Insert the plunger into the clamp
Remove the screwdriver

3.2 B2CF

Rigid wire
With plunger
Flexible wire
:important:The plunger to be used with the B2CF connectors must be long at least 12mm